Rờ Le Bảo Vệ Pha Và Bảo Vệ Mất Dây Trung Tính MAC04D0100 Giá Tốt
Trip
Settings
Phase Loss
Yes
Phase Sequence
Yes
Phase Asymmetry
94V ± 4V (Ph-Ph)
Under Voltage
55% to 95%
Over Voltage
105% to 125%
Hysterisis
7 V (± 2 V)
Time
Delay
ON Delay
5 s ±1 s (Fixed)
Trip Time
(OFF Delay)
For Phase failure phase Imbalance
Under voltage / Over Voltage 5 s ±1 s (Fixed)
For Neutral Fail 500 ms -1s
Output
Relay Output
2 C/O
Contact Rating
5A @ 240 VAC / 28 VDC (Resistive)
Electrical Life
1X10
Mechanical Life
1X10
Utilization Category
AC – 15
Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A
DC – 13
Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A
LED
Indications
on front plate
Power ON
Respective fault condition will be indicated by LED immediately & Relay will be tripped after specified trip time only.
GREEN
UV
OV
Blink: ASY, ON: REV
ON
OFF
OFF
OFF
Phase reverse
ON
OFF
OFF
ON
Asymmetry
ON
OFF
OFF
BLINK
UV
ON
ON
OFF
OFF
OV
ON
OFF
ON
OFF
Phase Fail
BLINK
OFF
OFF
OFF
Phase Fail *
BLINK
ON
OFF
BLINK
Neutral Fail
ON
BLINK
BLINK
BLINK
Phase fail indications when I/P voltages are below UV set point and below asymmetry
Operating Temperature
Storage Temperature
“-10 C To + 60 C
“-10 C To + 70 C
Humidity (Non Condensing)
95% (Rh)
Enclosure
Flame Retardant UL 94-V0
Dimension (W x H x D) (in mm)
36 X 90 X 60
Weight (unpacked)
120 g
Mounting
Base / DIN rail
Degree of Protection
IP 20 for Terminals, IP 40 for Enclosure